Get a Grip on Glove Inspection

Unless an employer has its own in-house electrical glove-testing program, testing gloves on the same day they are issued can be difficult to arrange. Several days, weeks, or even months may pass between electrical testing and issue to a worker. This gap can catch organizations off guard and may lead to violations of required retesting intervals if the relevant dates are not tracked correctly. So, how do we correct this?

OSHA’s Table I-5 identifies electrical testing requirements for rubber insulating gloves, including testing before first issue and every six months thereafter, as well as additional listed triggers. For gloves awaiting first issue, the footnote requires electrical testing within the preceding twelve months before they are placed into service. OSHA’s published interpretation discusses these requirements further.

OSHA’s August 19, 2020 interpretation, response two explains that first issue occurs when new gloves are removed from their original manufacturer’s packaging. OSHA considers them issued even if they are electrically tested and then returned to storage. Applying that interpretation, gloves that remain on the shelf for more than twelve months after their last electrical test and are then removed from their original packaging for retesting do not gain another twelve-month pre-first-issue storage allowance when they return. Retesting does not make them unissued again; the six-month retesting interval applies even if the employer has not yet handed them to a worker.

Andrew Olsen’s upcoming presentation raises practical questions about stock held on shelves and organizations rotating multiple sets of gloves. Those are useful program-management questions. The presentation’s suggestions for different intervals or exceptions are proposals; they do not create an allowance for overdue equipment.

The objective is a program that workers can follow and supervisors can verify. Any uncertainty about an interval should be resolved against the applicable requirements before equipment is issued, rather than after a rotation has put it back into service. Pre-use inspection and electrical retesting remain separate concepts for the purposes of this presentation.

Andrew Olsen will deliver the forty-five-minute presentation Say What You Mean at the 2027 IEEE IAS Electrical Safety Workshop, March 22–26, 2027, at the Peppermill Resort in Reno, Nevada. He will also lead the tutorial Five Frustrating DC Power System Safety Practices, covering DC energy challenges involving electric vehicles, solar PV, energy storage, power conversion, and data centers supporting AI. Join the workshop to continue these discussions with the electrical safety community. ElecTrain will also participate in the vendor exhibition. Stop by the ElecTrain booth to say hello and pick up some free giveaways.

2027 IEEE IAS Electrical Safety Workshop details

Source for the regulatory summary

OSHA glove-testing interpretation